Electronic Features
|
Control Panel |
Programmable |
Cooling Capacity
|
Rating Conditions: 95°F @ 60% RH |
60,000 Btu/h |
Electrical Characteristics
|
Voltage Requirement (60 Hz) |
1 Phase, 208/230 V |
Total Power Consumption |
6.6 kW |
Current Consumption |
31.5 amps* |
Recommended Fuse Size |
50 amps |
NEMA Plug Configuration |
6-50 |
Min. - Max. Voltage |
198 - 253 V |
Fans
|
Motor Output |
0.56 kW Evaporator
0.30 kW x 2 Condensers |
Evaporator
|
Fan Type |
Centrifugal |
Max. Air Flow - High/Mid/Low |
1770/1710/1650 CFM |
Max External Static Pressure |
0.9 IWG |
Condenser
|
Fan Type |
Centrifugal |
Max. Air Flow - High/Mid/Low |
2400 CFM |
Max. External Static Pressure |
0.85 IWG |
Compressor
|
Type |
Hermetic Rotary |
Output |
3.45 kW |
Refrigerant
|
Type |
R-410A |
Dimensions
|
W x D x H |
31 x 55 x 64 in |
Weight
|
Net / Shipping |
582 / 666 lb |
Power Cord
|
Gauge |
6 AWG (3-core) |
Length |
6 ft |
Condensate Tank
|
Auto Pump |
Included |
Operating Conditions
|
Min. - Max. @ 50% RH |
65° - 105°F |
Max. Duct Length
|
Per Cold Duct Hose |
40 ft |
Hot Duct Hose |
100 ft |
Max. Sound Level
|
With Condenser Duct - High/Mid/Low |
69/68/67 dB(A) |
Without Condenser Duct - High/Mid/Low |
71/70/69 dB(A) |
*Specification information shown with 230 V. |
Specifications subject to change without notice. All models feature compressor overload relay and fan motor protection. All models also feature compressor short-cycle protection, return air thermostat, automatic restart and accommodate a condensate pump kit. All portable models are 50 Hz-compatible with a slight performance decrease from specifications listed.
|
 |