Electronic Features
|
Control Panel |
Programmable |
Cooling Capacity
|
Rating Conditions: 95°F @ 60% RH |
60,000 Btu/h |
Electrical Characteristics
|
Voltage Requirement (60 Hz) |
3 Phase, 460 V |
Total Power Consumption |
6.6 kW |
Current Consumption |
12.2 amps |
Recommended Fuse Size |
20 amps |
NEMA Plug Configuration |
L16 - 20 |
Min. - Max. Voltage |
440 - 480 V |
Fans
|
Motor Output |
0.56 kW Evaporator
0.30 kW x 2 Condensers |
Evaporator
|
Fan Type |
Centrifugal |
Max. Air Flow - High/Mid/Low |
1770/1710/1650 CFM |
Max External Static Pressure |
0.9 IWG |
Condenser
|
Fan Type |
Centrifugal |
Max Air Flow |
2400 CFM |
Max. External Static Pressure |
0.85 IWG |
Compressor
|
Type |
Hermetic Scroll |
Output |
3.45 kW |
Refrigerant
|
Type |
R-410A |
Dimensions
|
W x D x H |
31 x 55 x 64 in |
Weight
|
Net / Shipping |
659 / 743 lb |
Power Cord
|
Gauge |
12 AWG (4 -core) |
Length |
6 ft |
Condensate Tank
|
Auto Pump |
Included |
Operating Conditions
|
Min. - Max. @ 50% RH |
65° - 105°F |
Max. Duct Length
|
Per Cold Duct Hose |
40 ft |
Hot Duct Hose |
100 ft |
Max. Sound Level
|
With Condenser Duct - High/Mid/Low |
69/68/67 dB(A) |
Without Condenser Duct - High/Mid/Low |
71/70/69 dB(A) |
Specifications subject to change without notice. All models feature compressor overload relay and fan motor protection. All models also feature compressor short-cycle protection, return air thermostat, automatic restart and accommodate a condensate pump kit. All portable models are 50 Hz-compatible with a slight performance decrease from specifications listed.
|
 |